Myers® P50 and P100 Series Effluent S.T.E.P. Pumps



Capacity : 60 gpm (227 lpm)
Head : 124 ft (37.8 m)


1/2 and 1 HP

The Myers P Series Effluent Pumps are designed specifically for today's multi-pump pressure collection and septic tank effluent pumping (S.T.E.R) systems and high head drainage applications. The P Series effluent pumps with their high efficiency single vane, enclosed impellers provide the steep non-overloading performance curves ideal for pressure collection and S.T.E.P systems. Myers 1/2 and 1 horsepower P Series pumps deliver more capacity at higher heads than most 1,1 1/2 and 2 horsepower pumps in their class. Myers P Series pumps are constructed of only the highest quality corrosion resistant materials like cast iron, stainless steel and thermoplastics to assure that they will perform for years to come in the harsh effluent environment end drainage applications.

Advantages By Design
Optimum performance for use in multi-pump pressure collection and S.T.E.P. systems
  • High efficiency, single vane, enclosed impeller provides non-overloading performance over entire range. Outperforms most pumps in its class.
  • Impeller passes 3/4 inch spherical solids.
  • Enclosed impeller design eliminates possibility of jamming or corrosion between impeller and volute.
Durable motor will deliver many years of reliable service
  • Oil-filled motor for maximum heat dissipation and constant bearing lubrication.
  • High torque, permanent split capacitor (PSC), single phase motors. No starting switches or relays to wear out.
  • Double tandem seal option for extra motor protection, tough effluent pumping applications.
  • Optional seal leak probe warns of seal leak condition. (Dual seal motors only.) Helps prevent costly motor damage.
  • On-winding current and temperature sensitive overload to protect against costly burnout due to overload.
The P series effluent pumps are designed for years of maintenance free operation
  • Volute seal ring is replaceable. Restores pump to original performance if wear should occur.
  • Motor is held in place by four screws. Easily removed if service is ever needed.





Specifications  · Construction Material  · Agency Approvals

Specifications

Head

124 ft
37.8
m

Maximum Spherical Solids

3/4 in
19
mm

Liquids Handling

Domestic Effluent & Drain Water

Intermittent Liquid Temperature

up to 140 ºF
up to 60
ºC

Motor Electrical Data

1 hp, 230 volts, 1 ph
oil-filled, permanent split capacitor type, 3450 rpm, 60 Hz

1/2 hp, 115 or 230 volts, 1 ph
oil-filled, permanent split capacitor type, 3450 rpm, 60 Hz

Motor Insulation

Class B(130°C)

Acceptable pH Range

6 to 9

Specific Gravity

0.9 to 1.1

Viscosity

28 to 35 SSU

Discharge, NPT

1 1/2 in
38.1
mm

Minimum Sump Diameter (Simplex)

24 in
61
cm

Minimum Sump Diameter (Duplex)

36 in
91.4
cm

Speed

3450 rpm

Power

1 hp
1/2
hp

Capacity

60 gpm
227
lpm


Construction Material

Motor Housing Material

Cast Iron, Class 30, ASTM A48

Volute Material

Cast Iron, Class 30, ASTM A48

Enclosed Single Vane Impeller Material

Engineered Thermoplastic

Impeller Wear Ring Material

304 SST

Power Cord Material

20 ft. 16/3 SJOW/SJOW-A

Volute Seal Ring Material

Buna-N

Shaft Material

416 SST

Standard Shaft Seal Material

Single Carbon & Ceramic

Optional Lower Shaft Seal Material

Tungsten Carbide

Fasteners Material

300 series SST


Agency Approvals

Agency Approvals



 MORE IMAGES 

·  Dimensions (Myers® P50 and P100 Series Effluent S.T.E.P. Pumps)

·  Pump Performance (Myers® P50 and P100 Series Effluent S.T.E.P. Pumps)

·  Specifications (Myers® P50 and P100 Series Effluent S.T.E.P. Pumps)


 DOWNLOADS 

P50 and P100 Series Effluent S.T.E.P. Pumps
(PDF, 411KB)