The answer is yes 
what is the question? VisaMastercardDiscover Visa, Mastercard, and
Discover Accepted
All Categories > Control Systems & Instruments > Blue Ribbon > Blue Ribbon Controllers > Item # BD200  
Download PDF Download PDF     Printable Page     Email Email This Page     Save To Favorites Save To Favorites

Item # BD200, Blue Ribbon Bulldog BD200 Setpoint Pump Controllers



Dual setpoint controller that is easy to program. Controls submersible pumps in lift stations, and is designed to field calibrate the Birdcage Level Sensor.

Standard Features
  • Selectable pump alternation when used with two pumps to minimize pump wear. With alternation "On", a seal failure or over-temperature condition will force the non-failed pump to lead status and stop alternation.
  • Alarm light for seal failure when used with a sumersible pump that includes a moisture sensor.
  • Alarm light for overheating when used with a pump that includes a thermostat. Pump is removed from service and can be brought back online manually or automatically when pump has cooled down.
  • Runtime displayed by a front panel button.
  • 24 VDC power for level transmitter
  • 4 - 20 mA or voltage signal
  • Nonvolatile memory, no batteries
  • Test System function that simulates the process input to test programming or to insure the pumps are operating.
  • User-selectable security lock-out of programming and/or setpoints.
The Bulldog BD200 Pump Controller provides versatile level control in a standard 1/4 DIN package.

This controller is versatile, simple, and inexpensive making it the ideal instrument for controlling dual pump lifting stations. Setpoints for ON/OFF and HI/LO alarms are easily set on the front panel. These same buttons also Enable/Disable pump alternation. Selectable time delay up to 60 seconds on power up for pump two prevents both pumps from starting at the same time and a large current draw. Alarms for pump seal failure and motor windings overheating are indicated by lights on the front panel. The dial can also display a runtime clock for each pump. An isolated 4-20 mA retransmission is standard. The front face is rated NEMA-4X for outdoor panel mounting. The BD-200 is also available with RS-232 or RS-485 protocol for connectivity with SCADA systems.





Specifications  · Agency Approvals

Specifications

Input

2 (or 0) to 10 VDC selectable
4 (or 0) to 20 mADC

Input Impedance

Current = 10 ohms, Voltage = 100 K ohms

Output Ratings

Control Relays: SPDT, 10A @ 240 VAC resistive, 1/4 hp @ 120 VAC, 1/3 hp @ 240 VAC Alarm Relays: SPST, 3A @ 240 VAC resistive, 1/10 hp @ 120 VAC

Control Type

Direct (pump in) acting
On/Off, reverse (pump out)

Accuracy

± 0.25% of span ± 1 least significant digit

Display

Two 4 digit, 7 segment, 14.2mm (0.56") high LED's

Resolution

1 count

Power Consumption

7.5 VA maximum

Electrical Supply

100 to 240 VAC nominal, +10% to 15%, 50 to 400 Hz single phase; 132 to 240 VDC +10% to 15%

Loop Powered Supply

isolated +24 VDC @ 50mA, regulated

Operating Temperature Range

-10 to 55 ºC
-14 to 130
ºF

Storage Temperature Range

-40 to 80 ºC
-40 to 175
ºF

Humidity Range

0 to 90% up to 40ºC for non-condensing

Seal Failure (Moisture Sensor)

Power: 2.5 VDC
Resolution: 10K to 500K ohms in 10K ohm steps

Search Current: 3 micro amps

Memory Backup

Non-volatile memory, no batteries

Panel Cutout

92 x 92 mm
3.622 x 3.622
in

Weight

454 g
16
oz

Front Panel Rating

IP66 (Type NEMA 4X)

Options

RS-232 or RS-485 with Mod bus protocol; Ethernet using TCP/IP

Accessories

Weatherproof Enclosures, NEMA 4X


Agency Approvals

Agency Approvals



 DOWNLOADS 

Bulldog BD200 Setpoint Pump Controller
(PDF, 76KB)