The answer is yes 
what is the question? VisaMastercardDiscover Visa, Mastercard, and
Discover Accepted
All Categories > Industrial Pumps & Meters > Flow Meters > BadgerMeter > Item # 1035  
Download PDF Download PDF     Printable Page     Email Email This Page     Save To Favorites Save To Favorites

Item # 1035, BadgerMeter Recordall® Compound Series Meters



Badger Meter offers the 3" Compound Series meter in Cast Bronze and a Low Lead Alloy. The Low Lead Alloy (Trade Designation: Compound Series LL-NS) version complies with NSF/ANSI Standard 61 and carries the NSF-61 Mark on the product.

Applications: For use in measurement of potable cold water in commercial and industrial services where flow is in one direction only.

Operation: At low flow rates, the water is diverted up through a bypass to the disc chamber. Leaving the chamber's outlet port, water flows beyond the turbo and main valve. As the flow rate increases, a pressure differential is created which opens the main valve. The water then flows straight through the turbine chamber in addition to a portion still flowing through the disc chamber before exiting the meter. Rotor and disc movement are transmitted by magnetic drive couplings to individual register odometers.

Operating Performance: With it's patented design, the Badger® Recordall Compound meter meets or exceeds registration accuracy for low flow rate, normal operating flow rates, maximum continuous operation flow rate, and changeover flow rate as specifically stated in AWWA Standard C702.

Construction: Badger Recordall Compound meter construction which complies with ANSI and AWWA C702 standards, consists of three basic components: meter housing, interchangeable measuring elements and single, sealed direct reading registers. The measuring element consist of the disc measuring chamber, turbo head assembly and high flow valve assembly.

To simplify maintenance, the registers and measuring elements can be removed without removing the meter housing from the installation.

Magnetic Drive: Direct magnetic drive, through the use of high- strength magnets, provides positive, reliable and dependable register coupling for straight-reading or remote reading options.

Sealed Registers: The standard registers consists of a straight- reading odometer-type totalization display, 360° test circle with center sweep hand and flow finder to detect leaks. Register gearing consists of self-lubricating thermoplastic gears to minimize friction and provide long life. Permanently sealed; dirt, moisture, tampering and lens fogging problems are eliminated. Multi-position register simplifies meter installation and reading. Automatic meter reading and close proximity systems are available for all Compound Series meters. (See back of sheet for additional information.) All reading options are removable from the meter without disrupting water service.

Meter Reading Technologies: The Itron® ERT®, ORION® and TRACE® meter reading systems are available for all Recordall Compound Series meters. An optional summator or Read-o-Matic®summator/converter can be provided as an integral part of the register assembly. (See back of sheet for additional information.)

Tamper-Proof Features: Tamper resistant register provides protection from unauthorized personnel.

Strainer: A separate strainer is recommended to protect the measuring element but is not a requirement. See Technical Brief PS-T-1 for strainer dimensions.

Maintenance: Badger Recordall Compound meters are designed and manufactured to provide long-term service with minimal maintenance.

When maintenance is required, it can be performed easily either at the meter installation or at any other convenient location. As an alternative to repair by the utility, Badger offers various maintenance and meter component exchange programs to fit the needs of the utility.

Connections: Companion flanges for installation of meters on various pipe types and sizes are available in cast iron or bronze as an option.

Standard: 3/4" drain plug.





Specifications  · Construction Material  · Proper Installation

Specifications

Type

Cold Water

Size

3" (DN 80 mm)

Typical Operating Range (100% ±1.5%)

1/2 - 450 gpm
0.1 to 102
m³/h

Maximum Continuous Flow

400 gpm
90.3
m³/h

Pressure Loss at Maximum Continuous Flow

0.41 bar at 90.3 m³/h
6.0 PSI at 400 gpm

Pressure Loss at Crossover

4 psi
0.28
bar

Minimum Crossover Accuracy

97 %

Maximum Operating Pressure

150 psi
10
bar

Maximum Operating Temperature

120 ºF
49
ºC

Meter Flanges

3" Round Flanges, Class 150

Register Type

Automatic Meter Reading and Close Proximity units optional.
Straight reading, permanently sealed magnetic drive standard

Low Flow Registration

1/4 gpm
0.06
m³/h
1,000,000 Cubic Feet (1 cubic ft./sweep hand revolution.)

10,000,000 Gallons (10 gallons/sweep hand revolution.)

100,000 m³/sweep hand revolution. (0.1 m³/sweep hand revolution.)

High Flow Registration

1,000,000 m³ (1 m³/sweep hand revolution.)
10,000,000 Cubic Feet (10 cubic ft./sweep hand revolution.)

100,000,000 Gallons (100 gallons/sweep hand revolution.)


Construction Material

Housing and Cover Material

Cast Bronze (B81), Low Lead Alloy

Turbo Cast Head Material

Cast Bronze (B81), Low Lead Alloy

Nose Cone and Straightening Vanes Material

Thermoplastic

Rotor Material

Thermoplastic

Rotor Radial Bearings Material

Lubricated Thermoplastic

Rotor Thrust Bearings Material

Sapphire Jewels

Rotor Bearing Pivot Material

Passivated 316 Stainless Steel

Calibration Mechanism Material

Stainless Steel And Thermoplastic

Measuring Chamber and Disc Material

Thermoplastic

High Flow Valve Material

Thermoplastic / Stainless Steel

Magnet Material

Ceramic

Register Lens Material

Glass

Register Housing and Cover Material

Thermoplastic or Bronze

Trim Material

Stainless Steel


Proper Installation
The following installation guidelines will insure optimum field performance and reliability when installing a Badger® Compound Series meter.
  • A Strainer IS REQUIRED to insure optimum flow conditioning and protection for the Compound Series meter measuring element.
  • Compound meters, with a strainer, REQUIRE a minimum of five (5) pipe diameters of straight pipe upstream of the meter.
  • ONLY full-open gate valves should be used immediately upstream of the meter. Butterfly valves MUST be five (5) pipe diameters or more upstream of the meter. Full-open gate or butterfly valves can be used downstream.
  • DO NOT install pressure reducing devices or check valves upstream of the meter.
  • Unweighted check valves MUST be located at least three (3) pipe diameters downstream of the meter.
  • Pressure reducing devices and externally weighted check valves MUST be located at least five (5) pipe diameters downstream of the meter.




 MORE IMAGES 

·  Badger Meter Recordall® Compound Series Meter-1

·  Pressure Loss/Accuracy Chart Badger Meter Recordall® Compound Series Meter)

·  Low/High Flow Meter (Badger Meter Recordall® Compound Series Meter)


 DOWNLOADS 

Recordall® Compound Series Meter
(PDF, 301KB)